commercialhvacuk

Cost guide

Commercial Chiller and Chilled-Water Cost

On most chilled-water projects the chiller is a minority of the total. Understanding where the rest of the money goes is what makes competing bids comparable.

Chilled-water cost at a glance

Indicative cost
Small packaged units are list-priced (table below); large chillers and complete chilled-water systems are quote-only
Chiller share of total
Often a minority once pumps, pipework and terminals are counted
Where chillers win
Larger buildings and central plant; the crossover with VRF depends on the building and its distribution
Big efficiency lever
Free cooling — uses low outside air temperature instead of the compressor
Extra compliance cost
ACOP L8 Legionella control on water-cooled and evaporative plant

The number that misleads

A chiller price on its own tells you little. Pumps, pipework, terminal units, plant-room work, controls, commissioning and — on water-cooled systems — the cooling tower and its water-treatment regime frequently add up to more than the chiller itself.

Where chilled water becomes the right answer

Chilled water generally starts to make sense as the building and its cooling load grow, and the threshold is not rigid. Two other factors push toward it independently of duty.

Refrigerant volume. A large direct-expansion system distributes refrigerant throughout the building, and above a certain size that becomes a significant issue in its own right — both for the mandatory F-Gas leak-checking regime, whose frequency scales with charge in tonnes of CO2 equivalent, and for BS EN 378 charge limits where mildly flammable A2L refrigerants are used. A chiller confines the refrigerant to the plant room and circulates water instead, which sidesteps both.

Buildings with many small rooms. Because A2L charge limits are set by the volume of the smallest room a system serves, hotels, care homes and cellular office buildings can hit that ceiling with a direct-expansion system. Chilled water avoids it entirely, which is increasingly a reason to choose it. See air conditioning replacement.

Small chiller prices: what is published

Chillers above about 60 kW are quote-only in the UK, and so are complete chilled-water systems. Below that, one air-cooled cooling-only range carries public list prices, and it shows how the price per kW falls with size.

Unit (air-cooled, cooling only)Cooling capacity, kWPrice ex VATSeller (source)
Daikin Applied EWAQ005BVP5£2,348.60Orion Air Sales
Daikin Applied EWAQ010ACV3P10£2,400.00 to £3,151.01ABC Direct / Orion Air Sales
Daikin Applied EWAQ016CWN16£4,428.64Orion Air Sales
Daikin Applied EWAQ025CWN25£7,622.48Orion Air Sales
Daikin Applied EWAQ032CWN32£7,939.15Orion Air Sales
Daikin Applied EWAQ050CWN50£11,781.42Orion Air Sales
Daikin Applied EWAQ064CWN63£13,519.53Orion Air Sales

Prices as displayed on the sellers’ pages on 30 September 2026, equipment only, excluding VAT at 20% and excluding delivery, installation, ductwork or pipework, controls beyond those listed, and commissioning. Sellers change prices without notice; the links are the source. This is what is published, not an average and not a quote.

Per kilowatt of cooling that runs from about £470 at 5 kW to about £215 at 63 kW, and the same 10 kW model is listed 24% apart by two sellers, so treat any single figure as a point in a range. For larger plant the only public numbers are budget guides: one asset-finance broker’s undated guide (Lendus) puts a 120 kW air-cooled chiller at £35,000 to £55,000, which is a project budget rather than a list price and is not something this page can verify.

What the money is actually spent on

People ask for a chiller price and receive one, then find the project costs several times that. The chiller is one line in a system.

  • The chiller itself — air-cooled or water-cooled, with or without free cooling, and with whatever resilience arrangement is specified.
  • Pumps, usually with standby, plus variable-speed drives.
  • Distribution pipework throughout the building, insulated, with valves and commissioning sets. On a large or occupied building this is frequently the biggest single line.
  • Terminal units — fan coil units, chilled beams or air handling unit coils — plus their controls and their own installation.
  • Plant-room work: structural support, anti-vibration, electrical distribution, drainage, and often ventilation for the plant room itself.
  • Controls and BMS integration, which on a chilled-water system is a substantial scope — sequencing multiple chillers, optimising flow temperature, and staging free cooling.
  • Commissioning and balancing, a major exercise on a water system and one that determines whether the design performance is ever achieved.
  • On water-cooled systems: the cooling tower or evaporative condenser, its water treatment, and the ongoing ACOP L8 Legionella management regime.

Air-cooled or water-cooled — the cost trade

Air-cooled chillers reject heat straight to the atmosphere through a coil. They are simpler, cheaper to install, need no water treatment and carry no Legionella duty. They are less efficient than water-cooled equivalents, particularly on hot days, and they are physically larger for a given duty.

Water-cooled chillers reject heat into a water circuit served by a cooling tower or evaporative condenser. They are more efficient and more compact, and they cost more to install and considerably more to operate as a regime — because the cooling tower brings ACOP L8 Legionella control with it: a written risk assessment, a water treatment programme, monitoring, sampling and record-keeping. That is a real, permanent operational cost and it needs to be in the comparison, not discovered afterwards. The guide to cooling tower legionella duties sets out what that regime asks of an owner.

For many UK commercial buildings the higher efficiency of water-cooled plant does not outweigh the installation cost and the L8 regime, which is why air-cooled dominates outside larger or more specialised applications. It is a genuine engineering judgement rather than a default.

Free cooling: the efficiency measure that pays for itself

The most valuable option on a UK chiller is usually free cooling, and its economics are unusually favourable here because of the climate.

The principle is straightforward: for a large number of hours in a British year, the outside air is cooler than the water returning from the building. When that is true, the system can reject heat directly through a coil without running the compressor at all — or run it at reduced load in partial free-cooling mode. Since the compressor is where most of the energy goes, the saving is substantial.

Free cooling costs more up front, in equipment and in physical size. It pays back best on loads that run through the cooler months — which is exactly the profile of data suites, comms rooms and process cooling, where cooling is needed in January as much as in July. On a purely seasonal comfort-cooling load that only runs in summer, the payback is much weaker, because the free-cooling hours largely fall when the plant is off anyway.

That distinction is the useful one: match the option to the load profile rather than treating free cooling as universally worthwhile. See commercial chillers and server room cooling.

The minimum efficiency a new chiller must meet

Since 1 January 2021 a comfort chiller placed on the market in Great Britain must meet the tier-2 seasonal space cooling energy efficiency (ηs,c) minimums in Table 4 of Regulation (EU) 2016/2281, retained in UK law. Ask every bidder for the declared ηs,c or SEER and check it against these floors.

Chiller typeRated capacityMinimum ηs,c
Air-to-water, electricunder 400 kW161%
Air-to-water, electric400 kW and above179%
Water or brine-to-waterunder 400 kW200%
Water or brine-to-water400 kW to under 1,500 kW252%
Water or brine-to-water1,500 kW and above272%
For comparison: air-to-air air conditioner (non-rooftop)any189%
Rooftop air conditionerany138%

A percentage above 100 is not a mistake: ηs,c expresses seasonal cooling delivered against electricity used, corrected for the primary energy factor, so 161% is the floor, not a good result. Manufacturers must also declare the unit’s outdoor sound power level.

Resilience, and what it costs

Central plant concentrates risk: when the chiller stops, the whole building loses cooling. How much that matters determines what you should spend on resilience.

Options run from a single chiller — cheapest, and a single point of failure — through multiple smaller chillers, which is often the sweet spot because it gives partial redundancy and better part-load efficiency, since running two of three machines at moderate load beats running one large machine at 30%, to a full N+1 arrangement where a spare machine covers any single failure.

The multiple-smaller-chillers approach is worth highlighting, because it is frequently the best value: you buy resilience and efficiency with the same money rather than treating them as separate purchases.

The ongoing costs to budget for

Energy dominates, and part-load efficiency — expressed as ESEER or an equivalent seasonal figure — matters much more than the full-load COP, because a chiller almost never runs at full duty. Maintenance on chilled-water plant is more involved than on a split system, covering the refrigeration circuit, the water side, pumps and controls. Water treatment applies to any wet system, and on evaporative plant the L8 regime is a substantial recurring commitment. F-Gas leak checking applies, and because chillers hold large refrigerant charges they typically sit in the more frequent checking bands. And water treatment and filtration on the chilled-water circuit protects the pipework and terminal units from corrosion and fouling — neglect here shows up years later as failed coils.

Illustrative running cost, with the assumptions shown. A 300 kW chiller delivering 1,000 equivalent full-load hours a year provides 300,000 kWh of cooling. At the legal minimum ηs,c of 161% for an air-to-water unit that takes about 186,300 kWh of electricity; at 179%, the floor for units of 400 kW and above, about 167,600 kWh. At the average price paid by a medium-sized non-domestic consumer in the second quarter of 2026, 24.61p/kWh excluding the Climate Change Levy (DESNZ, table 3.4.1), that is roughly £45,900 against £41,200 a year: the efficiency tier alone is worth about £4,600 a year at that price, before free cooling or part-load performance are counted. Your hours, loads and tariff will differ; ask for the declared seasonal figure and run this sum on it.

F-gas leak checks: the intervals the law sets

Chillers hold large refrigerant charges, so most sit in the more frequent checking bands of the retained F-gas Regulation (EU) 517/2014, Article 4. The interval depends on the charge expressed in tonnes of CO₂ equivalent, and it halves in frequency where a leakage detection system is fitted.

Charge (tonnes CO₂ equivalent)Check at least everyWith a leakage detection system
5 to under 5012 months24 months
50 to under 5006 months12 months
500 and above3 months6 months

Hermetically sealed equipment labelled as such and holding under 10 tonnes CO₂ equivalent is exempt. Checks must be carried out by certified persons, and a leakage detection system is mandatory on equipment holding 500 tonnes CO₂ equivalent or more. Budget for the checks and the records as a running cost, and ask a used-chiller seller for the leak-check history before anything else.

Guides on this topic

Frequently asked questions

How much does a commercial chiller cost?

Large chillers and complete chilled-water systems are quote-only in the UK, and complete systems run well into seven figures on large or complex buildings; small packaged units carry published list prices (table above). The chiller itself is often a minority of that: pumps, insulated distribution pipework, terminal units, plant-room work, controls and commissioning frequently exceed it, and water-cooled systems add a cooling tower and its water-treatment regime.

When is a chiller better than VRF?

There is no fixed capacity threshold; the case strengthens as the building and its cooling load grow, and two situations point to chilled water regardless of duty: where the refrigerant volume of a direct-expansion system becomes a problem for F-Gas leak-check frequency, and in buildings with many small rooms, where BS EN 378 A2L charge limits — set by the smallest room served — constrain a direct-expansion design. A chiller keeps refrigerant in the plant room.

Is free cooling worth the extra cost?

It depends on the load profile. Free cooling uses low outside air temperature to reject heat without running the compressor, so it pays back strongly on loads that run through the cooler months — data suites, comms rooms and process cooling. On a purely seasonal comfort-cooling load that only runs in summer, the payback is much weaker because the free-cooling hours occur when the plant is off.

Air-cooled or water-cooled — which is cheaper?

Air-cooled is cheaper to install and to operate as a regime, needs no water treatment and carries no Legionella duty, but is less efficient and physically larger. Water-cooled is more efficient and more compact but costs more to install and brings ACOP L8 Legionella control with its risk assessment, treatment, monitoring and record-keeping — a permanent operational cost that must be in the comparison.

Do chillers need Legionella controls?

Water-cooled chillers with cooling towers or evaporative condensers do — ACOP L8 applies, requiring a written risk assessment, a water treatment programme, monitoring, sampling and records. Air-cooled chillers reject heat to atmosphere through a coil with no evaporative water and do not carry that duty, which is one of the reasons air-cooled dominates in UK commercial buildings.


See commercial chillers and chilled-water systems for the engineering detail, server room cooling for continuous loads, and the main cost guide for other systems. Or request a quote.

Sources and last checked

Every figure on this page was checked against the source listed on 30 September 2026.

How much does a 200 ton chiller cost?

A 200 ton chiller is about 703 kW of cooling (one ton of refrigeration is 3.517 kW), which in the UK is quote-only plant; the US dollar prices that dominate search results do not transfer. Ask for the declared ηs,c against the 179% minimum, the refrigerant and its charge, and the complete chilled-water system priced separately from the chiller.

How much does a 500 ton chiller cost?

About 1,758 kW of cooling, again quote-only in the UK. At that scale the chiller is a minority of the project: pumps, distribution, terminal units, controls, commissioning and, for water-cooled plant, the cooling tower and its Legionella regime usually cost more than the machine.

Is a used or refurbished chiller worth buying?

Only with its paperwork. Ask for the F-gas leak-check records and the refrigerant type: high-GWP refrigerants are being phased down, which affects future servicing cost, and a unit below today’s ηs,c floor cannot be placed on the market as new. Have the seasonal efficiency verified, not just the nameplate COP.

Can we hire a chiller instead?

Yes; temporary chillers are hired for plant failures, refurbishments and seasonal peaks, priced by the week with delivery, connection and fuel or power on top. Hire suits continuity, not a permanent load, where the running-cost sum above quickly favours efficient owned plant.

Get chiller and chilled-water quotes

Related guides

Get a quote
Get a quote